The nozzle is a critical part of a circuit breaker. PTFE has been used widely as a material for circuit breaker nozzle. PTFE has very high light reflectance, thermal and chemical stability, good electrical resistance and low loss factor. Although PTFE is better than any other polymers for nozzle material, it doesn't have good performance in the high temperature are environment. That is, the pure PTFE nozzle gets serious inner explosion as well as surface degradation when the high voltage and current are interrupted. It is necessary to fill the inorganic materials in PTFE to improve the endurance in high power equipment interrupting the high voltage and current.
The are resistance of PTFE composites increased with filler content and those values were different from the kinds of fillers. The are resistance of PTFE composites filled with BN was better than that of PTFE composites filled with Al₂O₃ or TiO₂. The most important factor of fillers seems to be the light reflectance in the ultraviolet region.