Supercooled type ice storage system with aqueous solution (or water) may have trouble with non-uniform release of supercooling even though it contributes to the simplicity of system and ecological improvement. The non-uniform release increases the instability of the system because it may cause an ice blockage in pipe or cooling part. In order to suppress the release of the supercooling, a cooling experiment was tried to an ethylene glycol(EG) 3 mass% solution corresponding with pressurization. Also, the frequency ratio of the release of the supercooling was measured to the pressurization from 101 to 505 ㎪. At results, the frequency ratio of supercooling release tends to decrease as the pressure of the aqueous solution increased in each cooling rate. Moreover, it tends to decrease as the cooling rate of the solution decreased in each pressure.